Assessing Bioaerosols in Elementary School Classrooms
K.H. Bartlett, Ph.D., S.M. Kennedy, Ph.D., M. Brauer, Sc.D., B. Dill, Ph.D., C.
VanNetten, Ph.D. K.H. Bartlett, Ph.D kbartlet@interchange.ubc.ca
A two year study of elementary school classrooms was begun in 1996. Data
collected included: number of occupants and patterns of occupancy, CO2 levels,
temperature and percent relative humidity (%RH), total particulate, and air
exchange rates using tracer gas (SF6). Indoor and outdoor bioaerosols were
collected using an Andersen N-6 impactor.
The effect of measured indoor air quality parameters and building
characteristics on the airborne concentrations of indoor bacteria and mesophilic
fungi were evaluated using multiple linear regression. The variable with the
highest predictive value for bacterial concentrations was indoor CO2
concentration, with the final equation having a R2 of 0.59. In contrast, outdoor
temperature had the highest predictive value for indoor mesophilic fungi with
the final equation having a R2 of 0.61.
Variables commonly measured during an indoor air quality investigation can be
used to understand bioaerosol concentrations. High commensal bacterial counts
are clearly related to inadequate ventilation of the occupied space. In a
similar manner, the use of mechanical or natural ventilation in buildings and
the concentration of fungi in the outdoor environment is related to indoor
fungal counts. These data would suggest that indoor air quality investigations
benefit from an integrated investigative approach.